Custom Home Assistant integration for ComAir HRUC-Plus 3 / Vent-Axia Sentinel Kinetic Advance MVHR ventilation units via Modbus RTU over TCP.
- 40 Entities: Comprehensive sensor and control coverage
- Config Flow UI: Add via Settings → Integrations (no YAML editing)
- BMS Settings: Configuration matches Vent-Axia Connect app
- Climate Control: HVAC-like entity with preset modes
- Energy Tracking: Integrated energy sensor for HA Energy dashboard
- Heat Recovery: Calculated efficiency sensor
- Translations: English, Slovak, Czech, Polish — terminology taken from the manufacturer's own manuals (Comair HRUC-Plus NL and PL editions)
| Platform | Count | Entities |
|---|---|---|
| sensor | 20 | Temperatures (4), Humidity (2), CO2 (2), Fan RPM (2), Fan Speed % (2), Power, Energy, Heat Recovery, Timers (3), Diagnostics (3) |
| binary_sensor | 6 | Attention LED, Cooling Enable, Preheater Enable, Controlled Cooling/Heating, Summer Bypass |
| switch | 10 | Virtual Inputs 1-10 (BMS control mapping) |
| button | 1 | Sync Clock (write HA time to MVHR) |
| select | 1 | Ventilation Mode (Auto/Low/Medium/High/Boost) |
| number | 1 | Mode Duration (15-240 min, step 15) |
| climate | 1 | Ventilation with preset modes |
The unit publishes no documented summer-bypass flag, so Summer Bypass is inferred from
the air temperatures: when the bypass is open, supply tracks intake and exhaust tracks
extract. When intake and extract are within 3 °C of each other there is not enough signal to
judge, and the sensor reports unknown rather than guessing.
That inference has now been checked against a unit's own bypass status by a user on a
different model: when the bypass was genuinely open the sensor read on, and when it was
closed the sensor read off or unknown. So it is sound, with unknown as the honest
answer in the narrow-spread case rather than a wrong one.
The manual's own rule ("Zomer bypassmodus") is that the bypass engages only when the
indoor and outdoor thresholds are both exceeded and the outdoor temperature is below the
indoor temperature, and that it disengages as soon as either threshold is crossed back.
The sensor uses the necessary half of that: whenever intake is at or above extract the
damper cannot be open, so it reports a confident off instead of unknown. The
thresholds themselves are user-configurable on the unit and not exposed over Modbus, so
they are not assumed. unknown is now limited to the genuinely ambiguous band — outdoor
cooler than indoor, but by less than 3 °C.
The manual also describes bypass modes the bus cannot report: Off, Normal, Evening cooling (runs 5 hours, then reverts) and Night cooling (runs until the outdoor temperature rises again).
There is no register that reports the bypass directly. Register 30025, listed in the
official Gen V map only as "Other output sources… TODO/TBC", was tested as a candidate and
ruled out: it sits permanently at 1 on both an HRUC-Plus 3 VR and a Sentinel Econiq SC
while the real bypass opens and closes. The relay outputs 30021–30024 (cooling enable,
preheater enable, controlled cooling/heating) are not the bypass either — they appear to
drive external heating and cooling equipment and follow temperature.
The ComAir HRUC-Plus 3 (also sold as Vent-Axia Sentinel Kinetic Advance) is a whole-house heat recovery ventilation unit (MVHR) with built-in Modbus RS485 support via the BMS connector.
Supported models:
| Device | Variants | Tested |
|---|---|---|
| ComAir HRUC-Plus 3 | 250, 350 | 350 tested |
| Vent-Axia Sentinel Kinetic Advance | 250S/SX, 350S/SX (LH/RH) | 350SX RH tested |
| Vent-Axia Sentinel Econiq | SC | Tested — confirmed working by a user |
| Vent-Axia Sentinel Kinetic Apex | Gen V | Should work (same Modbus map) |
All Gen V units share the same Modbus register map, which is why models beyond the tested ones generally work. If you get another model running, please open an issue so it can be added here.
You need a WiFi or Ethernet RS485 gateway to bridge the unit's RS485 bus to your network. The gateway converts Modbus RTU (serial) to Modbus TCP (network).
| Gateway | Input Voltage | Interface | Tested |
|---|---|---|---|
| Elfin EW11A | 5-36V DC | WiFi | Yes |
| Waveshare RS485 to ETH | 5-36V DC | Ethernet | Should work |
| USR-W610 | 5V DC | WiFi | Should work |
The Elfin EW11A is recommended — it can be powered directly from the BMS connector (5V or 24V), requires no external power supply, and fits neatly inside the ventilation unit.
A standard RJ12 6-pin cable to connect the gateway to the BMS connector on the HRUC unit. You can use:
- RJ12 breakout adapter (recommended — clean, no soldering)
- Cut and strip an RJ12 cable
The HRUC-Plus has a 6P6C RJ12 BMS connector (J20) for Modbus RS485 communication.
Looking at RJ12 jack (clip facing down):
┌─────────────────────────┐
│ 1 2 3 4 5 6 │
│ 24V GND A B GND +5V │
└──────────┬──────────────┘
│
clip
| Pin | Signal | Description | Connect to Gateway |
|---|---|---|---|
| 1 | P24VF9 | +24V DC (fused 500mA) | VCC (if gateway supports 24V) |
| 2 | GND | Ground | (alternative GND) |
| 3 | MOD A | RS485 Data+ | A |
| 4 | MOD B | RS485 Data- | B |
| 5 | GND | Ground | GND |
| 6 | P5VF10 | +5V DC (fused 500mA) | VCC (if gateway needs 5V) |
HRUC BMS RJ12 (J20) Gateway Terminal
───────────────────── ────────────────────
Pin 1 or 6 (power) ──────── VCC
Pin 3 (MOD A) ───────────── A (Data+)
Pin 4 (MOD B) ───────────── B (Data-)
Pin 5 (GND) ───────────── GND
| Pin | Voltage | Use for |
|---|---|---|
| Pin 1 | 24V | Gateways rated 5-36V (e.g. Elfin EW11A) |
| Pin 6 | 5V | Gateways rated 5V only |
Both pins are fused at 500mA via F9 (24V) and F10 (5V).
The BMS board has a 120Ω terminator (R51) enabled via jumper J4:
- Enable if gateway is at end of RS485 bus
- Enable if cable length > 10 meters
- Enable if communication errors occur
This integration speaks Modbus RTU over TCP: Home Assistant builds the complete RTU frame (including the CRC) and the gateway must pass the bytes through unchanged. The gateway must therefore be a transparent serial bridge — it must not do Modbus protocol conversion.
| Setting | Value |
|---|---|
| Protocol | None (transparent) — see warning below |
| CLI | Disable — see warning below |
| Baud Rate | 115200 |
| Data Bits | 8 |
| Parity | None |
| Stop Bits | 1 |
| Flow Control | Disable or Half-Duplex — both confirmed working |
| Buffer Size | 512 |
| Gap Time | anywhere in 10–50 — both ends of that range confirmed working |
RS485 is a two-wire bus and therefore always half duplex; that is a property of the
wiring, not a setting you need to hunt for. The EW11A exposes a single Flow Control
dropdown in which Half-Duplex is one of the values, and either it or Disable works.
Frame Length and Frame Time are not on the Serial Port Settings page. They exist
only in the gateway's configuration export, and the defaults are fine — if you cannot find
them in the web interface, nothing is wrong.
| Setting | Value |
|---|---|
| Protocol | TCP Server |
| Local Port | 502 |
| Route | Uart |
| Security | None |
Two settings must be right, and both fail the same silent way.
Protocol =
None. The Elfin EW11A offersModbusin the Protocol dropdown. That mode makes the gateway expect Modbus TCP (MBAP-framed) requests from the network and silently discard the RTU frames this integration sends.CLI =
Disable. With CLI set toSerial Stringthe gateway watches the serial stream for its escape sequence (+++) so it can drop into command mode — meaning it inspects, and can absorb, bytes in transit. Modbus RTU is raw binary in which any byte pattern may occur, so a gateway hunting for a trigger string is not a clean pipe.Either mistake produces
No response received after 3 retrieswith perfect wiring. See Troubleshooting.
The values above are read from a working EW11A, not from a datasheet.
This is a correctly configured EW11A — note Protocol Settings → Protocol = None, which
is the setting that makes the gateway a transparent bridge:
Protocol Settings:
Route Settings:
The Modbus settings can be verified in the Vent-Axia Connect app under Advanced Settings → Modbus:
- Open HACS in Home Assistant
- Click Integrations
- Click the three dots menu → Custom repositories
- Add repository URL:
https://github.com/Koky05/comair-modbus-homeassistant - Select category: Integration
- Click Add
- Search for "ComAir HRUC-Plus Modbus"
- Click Download
- Restart Home Assistant
-
Download the latest release from GitHub
-
Copy the
comair_modbusfolder to your Home Assistant custom_components directory:config/ └── custom_components/ └── comair_modbus/ ├── __init__.py ├── climate.py ├── config_flow.py ├── const.py ├── coordinator.py ├── manifest.json ├── sensor.py ├── binary_sensor.py ├── select.py ├── number.py ├── strings.json └── translations/ ├── en.json ├── sk.json └── cs.json -
Restart Home Assistant
- Go to Settings → Devices & Services
- Click + Add Integration
- Search for "ComAir HRUC-Plus Modbus"
- Enter your gateway configuration:
| Field | Default | Description |
|---|---|---|
| Gateway IP Address | (required) | IP address of your Modbus gateway |
| Modbus TCP Port | 502 | TCP port for Modbus communication |
| Device ID (Slave Address) | 2 | Modbus slave address of the HRUC unit |
| Baud Rate | 115200 | Serial baud rate |
| Data Bits | 8 | Number of data bits |
| Parity | None | Parity setting |
| Stop Bits | 1 | Number of stop bits |
- Click Submit
The integration will test the connection and create all entities.
| Sensor | Register | Description |
|---|---|---|
| Intake Temperature | 30100 | Outside air entering the unit |
| Supply Temperature | 30110 | Heated/cooled air to rooms |
| Extract Temperature | 30120 | Room air being extracted |
| Exhaust Temperature | 30130 | Air being expelled outside |
| Sensor | Register | Description |
|---|---|---|
| Intake Humidity | 30101 | Outside air humidity (%) |
| Extract Humidity | 30121 | Room air humidity (%) |
| Intake CO2 | 30102 | Outside CO2 level (ppm) — if sensor installed |
| Extract CO2 | 30122 | Room CO2 level (ppm) — if sensor installed |
| Sensor | Register | Description |
|---|---|---|
| Supply Fan RPM | 30014 | Supply fan speed (RPM × 0.1) |
| Extract Fan RPM | 30016 | Extract fan speed (RPM × 0.1) |
| Power | 30010 | Current power consumption (W) |
| Energy | — | Accumulated energy (kWh), calculated from Power |
| Heat Recovery Efficiency | — | Calculated from temperatures (%) |
| Sensor | Register | Description |
|---|---|---|
| Run Time | 30001 | Total operating days |
| Service Timer | 30002 | Months until service required |
| Filter Timer | 30003 | Months until filter change |
| Faults | 30004-05 | Active fault codes |
| Warnings | 30006-07 | Active warning codes |
| Notifications | 30008-09 | Active notifications |
Control ventilation via the select entity or climate presets:
| Mode | Default Fan Speed | Description |
|---|---|---|
| Auto | Automatic | Automatic control based on sensors |
| Low | 20% | Low fan speed (PR1) |
| Medium | 30% | Medium fan speed (PR2, Normal) |
| High | 50% | High fan speed (PR3) |
| Boost | 100% | Maximum ventilation (PR4, Purge) |
Fan speeds are configurable per mode via the Vent-Axia Connect app.
The integration provides an Energy sensor (sensor.comair_hruc_plus_energy) that tracks total energy consumption in kWh. This sensor has state_class: total_increasing and can be used directly in the Home Assistant Energy dashboard.
A ready-to-use picture-elements Lovelace card that mimics the physical HRUC-Plus LCD controller display is included at docs/lovelace_controller_card.yaml.
Features:
- Transparent background (works with any HA theme)
- Outdoor/indoor temperature, humidity, heat recovery efficiency
- Mode-dependent fan icon (auto, speed-1, speed-2, speed-3, boost alert)
- Supply/extract fan speed percentages
- Air quality smiley (happy/neutral/sad based on faults/warnings)
- Power, energy, runtime, filter and service timers
Installation:
- Copy SVG icons from
docs/icons/to/config/www/comair/on your HA - Copy
docs/icons/lcd_transparent.pngto/config/www/comair/ - Dashboard → Edit → Add Card → Manual → paste content from
docs/lovelace_controller_card.yaml - Adjust the entity IDs. Home Assistant derives an entity ID from the entity's
translated name when it is first created, so they depend on the UI language you
installed with. The card ships with the IDs from a Slovak install
(
sensor.comair_hruc_plus_3_teplota_nasavania); on English you will havesensor.comair_hruc_plus_3_intake_duct_temperature. Search-and-replace before use.
The unit reports these as three 32-bit bitmasks. The Faults, Warnings and
Notifications sensors show the active codes as their state (OK, W-12, or
W-12, W-15), and carry the meaning of each one in attributes:
state: "W-12, W-15"
attributes:
codes: ["W-12", "W-15"]
descriptions:
- "W-12: Filter cleaning or replacement overdue"
- "W-15: BMS offline"The state stays a compact code list so automations and history keep working; the
descriptions are attributes, which is where a template or a card can pick them up.
An undocumented bit is passed through as raw hex (0x40000000) rather than hidden.
| Faults | Warnings | Notifications | |||
|---|---|---|---|---|---|
| F-1 | Supply air thermistor | W-1 | Supply air temperature | N-1 | Filter cleaning/replacement due soon |
| F-2 | Extract air thermistor | W-2 | Exhaust air temperature | N-2 | Service due soon |
| F-3 | Supply fan | W-3 | Preheated air temperature | N-3 | Device offline |
| F-4 | Extract fan | W-4 | Intake air humidity | N-4 | Cooling suspended |
| F-8 | Supply air too cold | W-5 | Extract air humidity | N-5 | Cooling insufficient |
| F-32 | HMI communication lost | W-6 | Supply air flow | ||
| W-7 | Extract air flow | ||||
| W-8 | Left filter sensor | ||||
| W-9 | Right filter sensor | ||||
| W-10 | System overpressure | ||||
| W-11 | Preheater activated | ||||
| W-12 | Filter cleaning or replacement overdue | ||||
| W-13 | Service interval overdue | ||||
| W-14 | Lost connection to sensors or controllers | ||||
| W-15 | BMS offline | ||||
| W-18 | Bypass or heat exchanger efficiency | ||||
| W-19 | Preheater IO offline | ||||
| W-20 | Cooling unit offline |
Sourced from the manufacturer's manuals, which do not cover the same set — the Dutch
edition documents F-8, W-18 to W-20 and N-3 to N-5 but omits W-8 and W-9; the Polish
edition (01/2024) documents W-8 and W-9 but omits the others. Two disagreements are
left as the Dutch edition has them and noted in const.py: it calls F-1 the supply
thermistor where Polish calls it the inlet thermistor, and W-2 the exhaust
temperature where Polish calls it the extract temperature.
How warnings clear, per the Dutch manual: W-1 to W-7, W-10, W-11 and W-20 clear once the unit recovers and is power cycled; W-12 and W-13 clear once the filter or service values are reset.
Older controllers use a different scheme. An earlier HRUC-Plus edition (manual 475340, same 10040001xx reference numbers) reports faults as additive numbers rather than F-/W-/N- codes —
01fan left,02fan right,04temperature sensor left,08right, and so on, summed together, so03means both fans. This integration reads the Gen V bitmask registers and decodes the F-/W-/N- scheme; if your controller shows plain numbers instead, it predates what these registers expose.
Before changing anything, run tools/gateway_test.py. It needs
only Python 3 (no Home Assistant, no pymodbus) and can run from any PC on the same
network, or from the Advanced SSH & Web Terminal add-on:
python3 tools/gateway_test.py 192.168.1.50It tests the TCP connection, sends a request in both RTU-over-TCP and Modbus TCP framing, sweeps device IDs 1–16, and prints which side of the chain is broken.
This error means the TCP connection to the gateway succeeded and the request was sent, but nothing came back from the RS485 side — complete silence rather than corrupted data. The network half of the setup is therefore already correct. Two possibilities remain, in order of likelihood:
1. The gateway never puts the request on the RS485 wire.
- Serial settings: Protocol = None. If it is set to
Modbus, the gateway expects Modbus TCP from the network and drops the RTU frames — this is by far the most common cause. - Network settings: Protocol =
TCP Server, Local Port =502, Route =Uart. - Confirmation: in
tools/gateway_test.py, if test 3 (Modbus TCP framing) gets a reply while test 2 (RTU over TCP) does not, the gateway is in conversion mode.
2. The request reaches the wire, but the unit does not answer.
- Open the gateway's status page and watch the serial Tx/Rx counters while the script runs. Tx increasing but Rx flat means the unit is not responding.
- Verify the wires are on the BMS RJ12 connector (J20). The connectors labelled
+ A B -are the sensor connectors and carry no Modbus. - Check GND is connected, not only A and B.
- Confirm the gateway is an EW11A (RS485, terminals A/B/C/D). The plain EW11 is RS232 and cannot talk to the unit.
- Try swapping A and B — but only after Protocol = None is confirmed, otherwise two variables change at once.
- Verify baud rate and parity match the Vent-Axia Connect app (Advanced Settings → Modbus): 115200 / 8 / None / 1.
The J4 terminator and alternative device IDs are not likely causes: a missing terminator does not produce total silence, and while the gateway is misconfigured every device ID fails, so sweeping IDs proves nothing.
- Verify gateway IP address is correct
- Check gateway is powered and on network:
ping <gateway_ip> - Verify TCP port 502 is accessible
- Verify the gateway is in TCP Server mode on port 502
- Check the gateway serial Protocol is
None, notModbus - Check Device ID is correct (default: 2)
- Verify RS485 wiring (A→A, B→B, GND→GND) on the BMS RJ12 connector
- Check gateway serial settings match (115200/8/N/1)
- Try enabling RS485 termination (jumper J4) if the cable is longer than 10 m
- Wait for first data poll (up to 30 seconds)
- Check Home Assistant logs for errors
- Verify Modbus communication with test script
- Your unit does not have CO2 sensors installed
- This is normal — the sensors will show as "Unknown"
With pymodbus available (inside the Home Assistant environment, for example). If you
do not have pymodbus, use tools/gateway_test.py instead — it
uses only the Python standard library.
from pymodbus.client import ModbusTcpClient
from pymodbus.framer import FramerType
client = ModbusTcpClient('192.168.x.x', port=502, framer=FramerType.RTU)
client.connect()
# Read intake temperature (device_id=2)
result = client.read_input_registers(address=99, count=1, device_id=2)
if not result.isError():
temp = result.registers[0] / 10
print(f"Intake Temperature: {temp}°C")
else:
print(f"Error: {result}")
client.close()- Home Assistant 2024.1.0 or newer
- pymodbus >= 3.6.0 (installed automatically)
| File | Description |
|---|---|
| BMS_WIRING_GUIDE.md | Detailed wiring instructions |
| MODBUS_CONFIRMED_SETTINGS.md | Confirmed Modbus register documentation |
| MODBUS_ANALYSIS.md | Modbus register map analysis |
- Peter Koval (@Koky05) — Development
- Vent-Axia / Ventilair — BMS pinout documentation and technical support
This project is licensed under the MIT License — see the LICENSE file for details.
Contributions are welcome! Please open an issue or pull request on GitHub.
This is an unofficial integration not affiliated with Vent-Axia or Ventilair. Use at your own risk.